Symmetrical fault currents · Impedance · Short-circuit MVA · Radial & Ring systems
IEC 60909
ℹCalculates max/min three-phase symmetrical fault current at the fault point using IEC 60909 voltage factor c. Includes source, transformer and feeder impedances in series.
System Parameters
Network / Source
MVA
Transformer
MVA
%
%
Feeder Cable / Line
Ω/km
Ω/km
km
Fault Results
Fault Currents
I″k3 — Three-phase fault
—
kA
Peak current ip
—
kA peak
Ith — Thermal equiv.
—
kA (1 s)
S″k — SC MVA
—
MVA
Total Impedance at Fault Point
Zk — Total
—
Ω
Rk
—
Ω
Xk
—
Ω
X/R ratio
—
—
Impedance Composition
Zsource—
Ztransformer—
Zcable/line—
Impedance Breakdown
Component
R (Ω)
X (Ω)
Z (Ω)
— Enter values and calculate —
Applied Formula
// IEC 60909 Eq. (29) — Three-phase fault
I″k3 = c · Un / (√3 · |Zk|)
ℹRing/loop distribution: fault current supplied from both ends simultaneously. Total I″k = IA + IB. Each path computed as radial equivalent per IEC 60909.
Common Parameters
%
Bus A — Source & Feeder
MVA
Ω/km
Ω/km
km
Bus B — Source & Feeder
MVA
Ω/km
Ω/km
km
Ring Fault Results
Path Contributions
Path A
—
kA
Path B
—
kA
Total at Fault Point
I″k total
—
kA
Peak ip
—
kA peak
S″k
—
MVA
Thevenin Zeq
—
Ω
System Diagram
Impedance per Path
Path
Zsrc (Ω)
Zcable (Ω)
Ztotal (Ω)
I (kA)
— Enter values —
Notes
// Path impedances in parallel (Thevenin equivalent)
Zeq = ZA ‖ ZB = ZA·ZB / (ZA+ZB)
IA = c·Un / (√3·ZA)
IB = c·Un / (√3·ZB)
Itotal = IA + IB
ℹTypical impedance values for common cables, transformers and overhead lines. Values referenced to the system voltage shown. Use these to populate the calculator inputs.
Power Transformers — ukr & uRr
Sn
ukr %
uRr %
X/R
100 kVA
4.0
1.8
2.2
250 kVA
4.0
1.4
2.8
630 kVA
4.0
1.1
3.6
1 MVA
5.0
1.0
5.0
2.5 MVA
5.5
0.8
6.9
10 MVA
6.0
0.5
12
40 MVA
8.0
0.3
27
100 MVA
12.0
0.2
60
250 MVA
14.0
0.1
140
Overhead Lines (Al conductor)
Size (mm²)
r' (Ω/km)
x' (Ω/km)
Imax (A)
50 Al
0.641
0.391
170
95 Al
0.306
0.371
250
150 Al
0.206
0.356
320
240 Al
0.125
0.340
420
400 Al
0.080
0.328
550
Underground Cables (XLPE)
Size (mm²)
r' (Ω/km)
x' (Ω/km)
Imax (A)
35 Cu
0.524
0.113
165
70 Cu
0.268
0.101
230
120 Cu
0.153
0.094
295
185 Cu
0.099
0.087
375
300 Cu
0.060
0.082
470
95 Al
0.320
0.099
195
150 Al
0.206
0.091
250
240 Al
0.125
0.086
320
400 Al
0.077
0.079
420
Voltage Factor c — IEC 60909 Table 1
Voltage Level
cmax
cmin
LV: 100V–1kV (±6%)
1.05
0.95
LV: 100V–1kV (±10%)
1.10
0.95
MV: 1kV–35kV
1.10
1.00
HV: 35kV–230kV
1.10
1.00
EHV: >230kV
1.10
1.00
IEC 60909 Key Equations
// Three-phase symmetrical fault current
I″k3 = c·Un / (√3·|Zk|)
// Peak short-circuit current
ip = κ·√2·I″k3
κ = 1.02 + 0.98·e−3R/X
// Thermal equivalent current (tk = 1s)
Ith = I″k·√(m+n)