Short Circuit & Fault Calculator

Symmetrical fault currents · Impedance · Short-circuit MVA · Radial & Ring systems

IEC 60909
Calculates max/min three-phase symmetrical fault current at the fault point using IEC 60909 voltage factor c. Includes source, transformer and feeder impedances in series.
System Parameters
Network / Source
MVA
Transformer
MVA
%
%
Feeder Cable / Line
Ω/km
Ω/km
km
Fault Results

Fault Currents

I″k3 — Three-phase fault
kA
Peak current ip
kA peak
Ith — Thermal equiv.
kA (1 s)
S″k — SC MVA
MVA

Total Impedance at Fault Point

Zk — Total
Ω
Rk
Ω
Xk
Ω
X/R ratio

Impedance Composition

Zsource
Ztransformer
Zcable/line
Impedance Breakdown
ComponentR (Ω)X (Ω)Z (Ω)
— Enter values and calculate —
Applied Formula
// IEC 60909 Eq. (29) — Three-phase fault
I″k3 = c · Un / (√3 · |Zk|)

// Peak current factor κ (IEC 60909 §4.3.1)
κ = 1.02 + 0.98 · e−3R/X
ip = κ · √2 · I″k3
Ring/loop distribution: fault current supplied from both ends simultaneously. Total I″k = IA + IB. Each path computed as radial equivalent per IEC 60909.
Common Parameters
%
Bus A — Source & Feeder
MVA
Ω/km
Ω/km
km
Bus B — Source & Feeder
MVA
Ω/km
Ω/km
km
Ring Fault Results

Path Contributions

Path A
kA
Path B
kA

Total at Fault Point

I″k total
kA
Peak ip
kA peak
S″k
MVA
Thevenin Zeq
Ω

System Diagram

Impedance per Path
PathZsrc (Ω)Zcable (Ω)Ztotal (Ω)I (kA)
— Enter values —
Notes
// Path impedances in parallel (Thevenin equivalent)
Zeq = ZA ‖ ZB = ZA·ZB / (ZA+ZB)

IA = c·Un / (√3·ZA)
IB = c·Un / (√3·ZB)
Itotal = IA + IB
Typical impedance values for common cables, transformers and overhead lines. Values referenced to the system voltage shown. Use these to populate the calculator inputs.
Power Transformers — ukr & uRr
Snukr %uRr %X/R
100 kVA4.01.82.2
250 kVA4.01.42.8
630 kVA4.01.13.6
1 MVA5.01.05.0
2.5 MVA5.50.86.9
10 MVA6.00.512
40 MVA8.00.327
100 MVA12.00.260
250 MVA14.00.1140
Overhead Lines (Al conductor)
Size (mm²)r' (Ω/km)x' (Ω/km)Imax (A)
50 Al0.6410.391170
95 Al0.3060.371250
150 Al0.2060.356320
240 Al0.1250.340420
400 Al0.0800.328550
Underground Cables (XLPE)
Size (mm²)r' (Ω/km)x' (Ω/km)Imax (A)
35 Cu0.5240.113165
70 Cu0.2680.101230
120 Cu0.1530.094295
185 Cu0.0990.087375
300 Cu0.0600.082470
95 Al0.3200.099195
150 Al0.2060.091250
240 Al0.1250.086320
400 Al0.0770.079420
Voltage Factor c — IEC 60909 Table 1
Voltage Levelcmaxcmin
LV: 100V–1kV (±6%)1.050.95
LV: 100V–1kV (±10%)1.100.95
MV: 1kV–35kV1.101.00
HV: 35kV–230kV1.101.00
EHV: >230kV1.101.00
IEC 60909 Key Equations
// Three-phase symmetrical fault current
I″k3 = c·Un / (√3·|Zk|)

// Peak short-circuit current
ip = κ·√2·I″k3
κ = 1.02 + 0.98·e−3R/X

// Thermal equivalent current (tk = 1s)
Ith = I″k·√(m+n)

// Short-circuit MVA
S″k = √3·Un·I″k3

// Network impedance from fault level
ZQ = c·Un² / S″kQ

// Transformer impedance (referred to LV)
ZT = KT·(ukr/100)·(Un²/Sn)
RT = KT·(uRr/100)·(Un²/Sn)
XT = √(ZT²−RT²)
Kappa Factor κ vs X/R
Fault Type Multipliers
Fault TypeMultiplierTypical I/Ik3
3-phase (L-L-L)1.00100%
3-phase-to-earth (L-L-L-E)≈1.00~100%
2-phase (L-L)√3/2 ≈ 0.866~87%
1-phase-to-earth (L-E)Depends Z060–120%
κ Factor Quick Reference
X/R ratioκip/I″k·√2
11.1281.128
21.2471.247
51.4681.468
101.6421.642
201.7601.760
501.8401.840
2.0002.000
Correction Factors
// Transformer correction factor KT
KT = 0.95·cmax / (1+0.6·xT)
where xT = ukr/100 (pu reactance)

// Generator correction KG
KG = Un·cmax / (UrG·(1+x″d·sin φrG))